How to pre-configure 'Motion sensor settings' prior to device commissioning using the Lumos Controls mobile app? (Hidden)
- Choose the zone from the top right corner of the app
- Go to the 'Devices' tab in the app
- Click on the '+' button and choose the option 'Add Device'
- Click on 'Commissioning Settings' and choose 'Motion sensor settings'
- Choose the sensor activation period during which the light device should be respond on receiving motion sensor triggers
-
- "When someone arrives": Defines the action to be performed when presence is detected
- Click on the
icon to choose the intensity level to be maintained on detecting presence. The default value will be 100%
- Also, configure the duration within which the lights should attain the chosen state. The default value will be 1 sec and can be configured between 0-12.5 sec
- "When everybody leaves": Defines the action to be performed when absence is detected
- Configure the duration for which the lights should remain in the state configured for 'When someone arrives'. The default value will be 20 min and can be configured between 0.5 - 1023 min if 'Min' is chosen and 1-30 sec if 'Sec' is chosen
- Click on the
icon to choose the intensity level to be maintained on detecting absence. The default value will be 0%
- Also, configure the duration within which the lights should attain the chosen state. The default value will be 1 sec and can be configured between 0-12.5 sec
- "Then": Defines the action to be performed later
- Configure the duration for which the lights should remain in the state configured for 'When everybody leaves'. The default value will be 20 min and can be configured between 0.5 - 1023 min if 'Min' is chosen and 1-30 sec if 'Sec' is chosen
- Click on the
icon to choose the custom intensity level to be maintained later. The default value will be 0%
- Also, configure the duration within which the lights should attain the chosen state. The default value will be 1 sec and can be configured between 0-12.5 sec
6. Enable the 'Manual override' option to configure the duration after which the light device should respond to the motion sensor triggers if it was manually controlled
- The default value for this interval is 10 sec and can be configured between 0-1270 sec
Note: During this period the lights will not respond to the sensor
You can also visit the following sections for more information:
To know how to Commission & Configure Control Devices, click here
To know how to Commission & Configure Sensors, click here
To know how to Commission & Configure Switches, click here
To know how to Commission & Configure Gateway, click here