Daylight Harvesting

How to Auto Calibrate the values for Open Loop using the Lumos Controls mobile app?

Daylight Harvesting

  1. Go to the 'Daylight sensor settings' of the sensor
  2. Click on the Add icon icon on the 'Light response curve' under 'Open Loop'
    tia5923868126693613976
  3. Enable the option 'Auto Calibration'
  4. Once enabled, auto calibration will be completed in 24 hours (will be disabled after 24 hours)
  5. The calibrated values can be read while auto calibration is in progress by clicking on the 'Read' button
  6. When auto calibration is completed, the least and the greatest values from the lot will be automatically configured as the Min and Max lux values
  7. Disable 'Auto Calibration' if you want to manually configure open loop values 

You can also visit the following sections for more information:

To know how to Commission & Configure Sensors, click here
To know how to Commission & Configure Control Devices, click here
To configure Motion Based Automation, click here
To configure Scenes & Animations, click here
To configure Light Schedules, click here
To know the Operations and Control details, click here